燃氣發電機啟停作業有很多要注意的地方,下面沼氣脫硫設備廠家就給大家總結了一下,希望大家都可以認真閱讀,對大家有所幫助!
Gas generator start-up and shut-down operation has a lot to pay attention to, below the methane desulfurization equipment manufacturers to summarize for you, I hope you can read carefully, to help you!
一、準備工作
I. Preparations
1、檢查燃氣發電機的預熱系統、水循環系統是否正常;
1. Check whether the preheating system and water circulation system of gas generator are normal.
2、檢查氣路上各閥門的狀態,檢查發電機通負載電路開關狀態;
2. Check the status of the valves on the gas path and the on-off status of the load circuit of the generator.
3、檢查發電機組是否固定牢固,各個電線接頭有無脫落。
3. Check whether the generator set is fixed firmly and whether the connection of each wire has fallen off.
4、檢查機組機油,冷卻水、電池液是否足夠,有無滲漏;
4. Check whether the oil, cooling water and battery liquid are enough and whether there is leakage.
5、檢查顯示屏上電池電壓,有無故障報警,若當前有故障報警,消除故障后,取消報警,否則發電機無法啟動;
5. Check the battery voltage on the display screen and alarm if there is a fault. If there is a fault alarm at present, after eliminating the fault, cancel the alarm, otherwise the generator can not start.
二、操作要求
II. Operational requirements
1、熟悉發電機操作步驟,嚴格執行本作業指導卡;
1. Familiar with generator operation procedures, strictly implement the operation guidance card;
2、啟動后必須定時觀測機組工作狀況。
2. The working condition of the unit must be observed regularly after start-up.
三、操作步驟
III. Operational steps
㈠ 啟動燃氣發電機
A Start-up Gas Generator
1、打開氣路上所有閥門,調整進發電機天然氣壓力至15mbar(1.5KPa)左右;
1. Open all valves on the gas path and adjust the natural gas pressure into the generator to about 15 bar (1.5 KPa);
2、旋轉控制面板上按鈕至“啟動”位置,啟動發電機;
2. Rotate the button on the control panel to the "start" position and start the generator.
3、機組啟動后檢查各參數顯示是否正常(電壓、頻率、水溫、油壓等),機組各部分有無滲漏;
3. Check whether the parameters of the unit are normal (voltage, frequency, water temperature, oil pressure, etc.) and whether there is leakage in each part of the unit after start-up.
4、閉合機組輸電開關,給負載供電;
4. Close the transmission switch of the unit to supply power to the load.
5、每30分鐘,記錄運行參數(水溫、油壓、電壓、電流等)。
5. Record operation parameters (water temperature, oil pressure, voltage, current, etc.) every 30 minutes.
㈡ 停燃氣發電機
Gas Generator with Two Stops
1、斷開發電機的負載開關,使機組空載運行5分鐘;
1. Disconnect the load switch of the generator to make the unit run for 5 minutes without load.
2、旋轉控制面板上按鈕至“停機”位置。
2. Rotate the button on the control panel to the stop position.
Well, today's wonderful content is introduced here. If you have any questions, please consult the official website customer service staff of biogas desulfurization equipment: http://www.477115.com.